1、 In China's power system, especially in the distribution network below 35KV, there are a large number of electromagnetic voltage transformers
Electromagnetic voltage transformers have nonlinear electromagnetic characteristics
When they match with the capacitive elements in the power grid, ferromagnetic resonance will occur, resulting in extremely high ferromagnetic resonance overvoltage
In case of overvoltage, the excitation current of the transformer is greatly increased due to the saturation of the iron core of the transformer, which is more than 100 times of the normal excitation current in serious cases, resulting in the fusing, oil injection, burning and even explosion of the fuse of the voltage transformer, which seriously threatens the safe operation of the power grid
At present, the primary harmonic eliminator is connected to the primary neutral point of the voltage transformer in the power grid to limit the ferromagnetic resonance overvoltage
However, it is often found that the PT secondary voltage imbalance occurs after the installation of the primary harmonic eliminator, and the secondary voltage imbalance basically disappears after the removal of the primary harmonic eliminator
Through detailed field measurement, calculation and analysis, it is found that the root cause of this phenomenon is the third harmonic in the power grid
Through the inductive reactance formula of the transformer (XL = 2 & PI; F), we can know that the higher the frequency, the greater the impedance of the transformer, so the greater the inductive reactance difference of the three transformers, When the third harmonic current flows through the excitation winding of the transformer and the primary harmonic eliminator, due to the different impedance, the neutral point displacement voltage is generated, resulting in the three-phase voltage imbalance
In order to solve the above problems, Anhui Yahui Electric Automation Co
, Ltd
has developed the patented yhptx voltage transformer third harmonic suppressor after years of research
The suppressor adopts the high computing speed CPU of American Weixing company as the core processing element, combined with modern power electronic control technology, which can effectively suppress the influence of the third harmonic current on the voltage transformer, Solve the problem of three-phase voltage imbalance after the primary harmonic eliminator is installed on the voltage transformer
2、 Rated parameters
2
1 working environment conditions
Ambient temperature: - 40 ~ + 65 ℃
Altitude: less than 5000m
Seismic intensity: less than 8 degrees
Relative humidity: no more than 95%, no condensation
Atmospheric pressure: 80 ~ 110kpa
Other conditions: the air around the device shall not contain acid, alkali corrosion or explosive substances, and lightning protection, rain and snow facilities shall be provided
2
2 rated electrical parameters
Working power supply: built-in (low-power design, service life greater than 20 years)
Rated input voltage: 100V
Frequency: less than or equal to 150Hz
2
3 overload capacity
1
2 times of rated input voltage can work for a long time
1
5 times the rated input voltage, allowing 2 hours
Contacts
- Company Name
- Anhui Yahui Electric Automation Co., Ltd
- Name:
- Mr. Lin Fei
- Q Q
- 2880909601
- Telephone
- 0551-63889111
- Mobile
- 13349293555
Address
- Operational Address
- Building B-4, industrial investment Liheng industrial Plaza, bustling Avenue, Taohua Industrial Park, Hefei Economic Development Zone, Anhui Province
Find Similar Products By Category
premiumexporter.com温馨提示
本网页所展示的有关【Yhptx third harmonic suppresso】的信息/图片/参数等由的会员【Anhui Yahui Electric Automation Co., Ltd】提供,由premiumexporter.com会员【Anhui Yahui Electric Automation Co., Ltd
】自行对信息/图片/参数等的真实性、准确性和合法性负责,本平台(本网站)仅提供展示服务,请谨慎交易,因交易而产生的法律关系及法律纠纷由您自行协商解决,本平台(本网站)对此不承担任何责任。您在本网页可以浏览【Yhptx third harmonic suppresso】有关的信息/图片/价格等及提供【Yhptx third harmonic suppresso】的商家公司简介、联系方式等信息。
在您的合法权益受到侵害时,请您致电,我们将竭诚为您服务,感谢您对premiumexporter.com的关注与支持!